AFTER DIVERSITY MAXIMUM DEMAND CALCULATOR

A very useful spreadsheet to calculate the maximum demand of an installation, after diversity has been taken into account. 

A print out can then be made for the project file to form part of the design data.

 
Project Title:  New hotel, New Town Development, Coventry

Diversity Allowances For Hotels And Guest Houses

Item ReferenceConnected Load    AmpsDiversity FactorLoad After Diversity Amps  L1   AmpsL2      AmpsL3      Amps
Lighting Total Current Demand 2175%15.8 5.0 5.05.8 
       
Heating / Power Largest Appliance Full Load60100%60.0 20.0 20.020.0 
Heating And Power 2nd Largest Appliance Full Load4080%32.0 11.0 12.011.0
Heating / Power Remaining Appliance Loads 60%0.0   
       
Cooking Appliances Largest Appliance
Full Load
15100%15.0 15.0  
Cooking Appliances Second Largest Appliance Full Load12 80%9.6  9.6 
Cooking Appliances Remaining Appliances 60%0.0   
       
Motors Largest (Other Than Lift Motors) Full Load10100%10.010.010.0  10.0
Motors Remainder (Other Than Lift Motors) Full Loads 50%0.0   
       
Water Heaters Instantaneous Largest  Appliance Full Load 12100%12.0   12.0
Water Heaters Instantaneous 2nd Largest Appliance Full Load 100%0.0   
Water Heaters Instantaneous Remaining Appliances Full Loads 25%0.0   
Water Heaters Thermostatic 100%0.0   
       
Final Circuits (Largest Circuit Load) 15100%15.0 15.0  
Final Circuits (Other Circuit Loads) 50%0.0   
       
Other loads:  0.0   
Other loads:  0.0   
Other loads:  0.0   
Other loads:  0.0   
 Total Load (Exc Off Peak)189.476.056.658.8
Heating Off Peak 

 

100%0.0   
Water Heating Off Peak100%0.0   
 Total Load  (Off Peak)0.00.00.00.0