AFTER DIVERSITY MAXIMUM DEMAND CALCULATOR
A very useful spreadsheet to calculate the maximum demand of an installation, after diversity has been taken into account. A print out can then be made for the project file to form part of the design data. |
| Project Title: New hotel, New Town Development, Coventry | ||||||
Diversity Allowances For Hotels And Guest Houses | ||||||
| Item Reference | Connected Load Amps | Diversity Factor | Load After Diversity Amps | L1 Amps | L2 Amps | L3 Amps |
| Lighting Total Current Demand | 21 | 75% | 15.8 | 5.0 | 5.0 | 5.8 |
| Heating / Power Largest Appliance Full Load | 60 | 100% | 60.0 | 20.0 | 20.0 | 20.0 |
| Heating And Power 2nd Largest Appliance Full Load | 40 | 80% | 32.0 | 11.0 | 12.0 | 11.0 |
| Heating / Power Remaining Appliance Loads | 60% | 0.0 | ||||
| Cooking Appliances Largest Appliance Full Load | 15 | 100% | 15.0 | 15.0 | ||
| Cooking Appliances Second Largest Appliance Full Load | 12 | 80% | 9.6 | 9.6 | ||
| Cooking Appliances Remaining Appliances | 60% | 0.0 | ||||
| Motors Largest (Other Than Lift Motors) Full Load | 10 | 100% | 10.0 | 10.0 | 10.0 | 10.0 |
| Motors Remainder (Other Than Lift Motors) Full Loads | 50% | 0.0 | ||||
| Water Heaters Instantaneous Largest Appliance Full Load | 12 | 100% | 12.0 | 12.0 | ||
| Water Heaters Instantaneous 2nd Largest Appliance Full Load | 100% | 0.0 | ||||
| Water Heaters Instantaneous Remaining Appliances Full Loads | 25% | 0.0 | ||||
| Water Heaters Thermostatic | 100% | 0.0 | ||||
| Final Circuits (Largest Circuit Load) | 15 | 100% | 15.0 | 15.0 | ||
| Final Circuits (Other Circuit Loads) | 50% | 0.0 | ||||
| Other loads: | 0.0 | |||||
| Other loads: | 0.0 | |||||
| Other loads: | 0.0 | |||||
| Other loads: | 0.0 | |||||
| Total Load (Exc Off Peak) | 189.4 | 76.0 | 56.6 | 58.8 | ||
| Heating Off Peak |
| 100% | 0.0 | |||
| Water Heating Off Peak | 100% | 0.0 | ||||
| Total Load (Off Peak) | 0.0 | 0.0 | 0.0 | 0.0 | ||